Loading...
HomeMy WebLinkAbout300-350 Airport Boulevard - PlansCCRL Cement and Concrete Reference Laboratory Inspection Report Introduction ww�v.ccrl.us This report covers the concrete masonry unit, concrete, and reinforcing bar inspection conducted in the laboratories of Mid Pacific Engineering, Incorporated, at West Sacramento, California. This inspection, designated as Inspection Number F-354, was completed in the laboratories on November 18, 2015. Inspections generally cover three areas: quality systems; testing equipment; and procedures. Under all material types inspected there will be a Summary of Findings and a Footnote Section. The Summary of Findings will denote items examined, which may include: documents, equipment and procedures performed by the laboratory. Entries in the Summary of Finding Section cover availability, physical condition, and/or conformance to specification requirements. These items, when checked, will indicate whether the items conformed to the ASTM standard or will state briefly any deviation from the standard and will be listed in the Footnote Section. The Footnote Section is also used to convey observations, recommendations ar explanations of conditions found. When a footnote of this nature appears in a report it is labeled as an "Informational Footnote" in bold font. These informational footnotes do not require deficiency corrections. Corrections of minor deficiencies are encouraged during the course of each inspection. In the interest of brevity, any adjustments of this nature which may have been made have not been mentioned in #he report. Several pieces of apparatus in the laboratory have been assigned CCRL identification numbers. Some of Yhese numbers are listed in the Summary and Footnote Sections. For a more in-depth description of the scope of each inspection, please see www.ccrl.us/Lio/lip.htm_ The inspection was conducted using the most recent version of the applicable Book of ASTM Standards available at the time of the inspection, unless otherwise indicated in the Footnote Section of this report. This report confirms the condition of the laboratory on the inspection date noted above. It does not approve, certify or accredit this laboratory; therefore, publicizing the inspection without offering a review of this report is prohibited. 4441 Buckeystown Pike, Suite C�: Fredenck, Maryland 21704 pltone: 240d36-4800 6+ faY: 610.8347066 0� email: arl�stmarg Sponsored by Comwittecs C-1 and G9 of AST'M International